NYCWY cables are robust low-voltage cables with a concentric conductor, suitable for power distribution in buildings, industrial facilities, and underground installations. Thanks to their PVC insulation and sheath, they are mechanically durable, moisture-resistant, and versatile in use – even in concrete or water.

NYCWY
NYCWY

Request a Quote

Get technical specifications and pricing for your project.

By submitting you agree to our privacy policy

Versatile use in power distribution

The NYCWY is one of the classic low-voltage cables according to VDE standard and is designed for rated voltages up to 1 kV. It is used wherever reliable energy distribution is required – in buildings, industrial plants, transformer stations, or directly underground. It can also be easily installed in cable trays, concrete environments, or underwater. The choice of materials ensures that this cable withstands even harsh conditions – without the need for additional protective measures.

Construction and materials

The design is technically well thought out: a copper conductor forms the core, surrounded by PVC insulation that is both mechanically robust and electrically safe. This is followed by a concentric conductor in a corrugated shape, which serves as a protective or return conductor depending on the application. The outer layer is a durable PVC sheath that protects the cable against moisture, pressure, and chemical influences.

Variants and cross-sections

The NYCWY is available in a wide range of versions – for example, 4x25/16, 4x70/35, or 4x185/95. The first number group indicates the number and cross-section of the current-carrying conductors, the second refers to the concentric conductor. This flexibility allows the cable to be adapted to different network requirements – from house connections to industrial power distribution.

Technical Specifications

General Data

Bending radius (mm)
15/12xD mm
CPR class
Eca
Maximal operating conductor temperature (°C)
70 °C
Maximal short-circuit temperature (°C)
160 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-5 °C
Operating temperature range (°C)
-35-+70 °C
Rated voltage (kV)
0.6/1 kV
Self-extinguishing of single cable
IEC 60332-1-2
Test voltage (kV)
4 kV

0.6/1 kV

Voltage
0.6/1 kV
Test voltage
4 kV
Operating temperature range
-35-+70 °C
Conductor temperature (max.)
70 °C
Short-circuit temperature (max.)
160 °C
Minimum laying temperature
-5 °C
Minimum storage temperature
-35 °C
CPR class
Eca
Flame retardant
IEC 60332-1-2
Config.Cond.ShapeRI [Ohm/km]Wi [mm]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
2x10/10CuRE1.8311.812xD19670
2x16/16CuRE1.1511.812xD21890
3x10/10CuRE1.8311.812xD20773
3x10/10CuRMV1.8311.812xD21817
3x16/16CuRE1.1511.812xD221045
3x16/16CuRMV1.1511.812xD221085
3x25/16CuRMV0.7271.21.812xD261490
3x25/25CuRMV0.7271.21.812xD261582
3x35/16CuSM0.5241.21.812xD261729
3x35/35CuSM0.5241.21.812xD261913
3x50/25CuSM0.3871.41.912xD292272
3x50/50CuSM0.3871.41.912xD302498
3x70/35CuSM0.2681.4212xD333128
3x70/70CuSM0.2681.4212xD343473
3x95/50CuSM0.1931.62.212xD384177
3x95/95CuSM0.1931.62.212xD384640
3x120/70CuSM0.1531.62.312xD415168
3x120/120CuSM0.1531.62.312xD415674
3x150/70CuSM0.1241.82.412xD466193
3x150/150CuSM0.1241.82.412xD476982
3x185/95CuSM0.099122.612xD507689
3x185/185CuSM0.099122.612xD518609
3x240/120CuSM0.07542.22.812xD569950
4x10/10CuRE1.8311.812xD21903
4x16/16CuRE1.1511.812xD241237
4x25/16CuRMV0.7271.21.812xD281801
4x25/25CuRMV0.7271.21.812xD281886
4x35/16CuSM0.5241.21.812xD282156
4x35/35CuSM0.5241.21.812xD282333
4x50/25CuSM0.3871.4212xD332944
4x50/50CuSM0.3871.4212xD343171
4x70/35CuSM0.2681.42.112xD363932
4x70/70CuSM0.2681.42.112xD374277
4x95/50CuSM0.1931.62.312xD425276
4x95/70CuSM0.1931.62.312xD425488
4x95/95CuSM0.1931.62.312xD425740
4x120/70CuSM0.1531.62.412xD466571
4x120/120CuSM0.1531.62.412xD467077
4x150/70CuSM0.1241.82.612xD517883
4x185/95CuSM0.099122.812xD569892
4x185/185CuSM0.099122.812xD5710813
4x240/120CuSM0.07542.2312xD6212658