Home
Low Voltage Cables

N2XY

The N2XY cable is an unarmoured low-voltage cable for power and control applications up to 0.6/1 kV. It is suitable for fixed installation in buildings, outdoors, in humid environments, and for direct burial – wherever no special mechanical stresses occur.

N2XY
N2XY

Request a Quote

Get technical specifications and pricing for your project.

By submitting you agree to our privacy policy

For fixed installation in standard applications

The N2XY is used in low-voltage systems for power distribution – for example in cable trays, conduits, on walls, or directly underground. It can be installed both indoors and outdoors and is also suitable for humid environments. Thanks to various core configurations (single-core to four-core) and cross-sections up to 630 mm², the cable can be flexibly adapted to the respective application.

Technical construction

The conductor consists of solid or stranded copper (RE or RM), with the cores insulated with XLPE (cross-linked polyethylene). The cable is embedded in a PVC filler compound and surrounded by a PVC outer sheath, which protects it against environmental influences and normal mechanical stress.

Variants and applications

N2XY is available as N2XY-J (with protective conductor) and N2XY-O (without protective conductor). It offers a space-saving, economical solution for low-voltage distribution without compromising on safety or quality. Typical applications include commercial and residential buildings, system installations, as well as connections between switchgear and distribution boards.

Technical Specifications

General Data

Bending radius (mm)
15/12xD mm
CPR class
Eca
Maximal operating conductor temperature (°C)
90 °C
Maximal short-circuit temperature (°C)
250 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-5 °C
Operating temperature range (°C)
-35-+90 °C
Rated voltage (kV)
0.6/1 kV
Self-extinguishing of single cable
IEC 60332-1-2
Test voltage (kV)
4 kV

0.6/1 kV

Voltage
0.6/1 kV
Test voltage
4 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
90 °C
Short-circuit temperature (max.)
250 °C
Minimum laying temperature
-5 °C
Minimum storage temperature
-35 °C
CPR class
Eca
Flame retardant
IEC 60332-1-2
Config.Cond.ShapeRI [Ohm/km]Wi [mm]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x10CuRE1.830.71.812xD9166
1x16CuRE1.150.71.812xD10229
1x25CuRMV0.7270.91.812xD12336
1x35CuRMV0.5240.91.812xD13436
1x50CuRMV0.38711.812xD14562
1x70CuRMV0.2681.11.812xD16774
1x95CuRMV0.1931.11.812xD181027
1x120CuRMV0.1531.21.812xD201267
1x150CuRMV0.1241.41.812xD221555
1x185CuRMV0.09911.61.812xD241922
1x240CuRMV0.07541.71.812xD262471
1x300CuRMV0.06011.81.812xD293055
1x400CuRMV0.04721.912xD323880
1x500CuRMV0.03662.2212xD364938
3x10CuRE1.830.71.812xD17581
3x16CuRE1.150.71.812xD19800
3x25CuRMV0.7270.91.812xD231193
3x35CuRMV0.5240.91.812xD261553
3x50CuSM0.38711.812xD261815
3x70CuSM0.2681.11.912xD302519
3x95CuSM0.1931.1212xD333319
3x120CuSM0.1531.22.112xD374089
3x150CuSM0.1241.42.312xD415077
3x185CuSM0.09911.62.412xD456233
3x240CuSM0.07541.72.612xD518067
3x25+16CuRMV/RE0.7270.9/0.71.812xD241357
3x35+16CuSM/RE0.5240.9/0.71.812xD261658
3x50+25CuSM/RMV0.3871.0/0.91.812xD292170
3x70+35CuSM0.2681.1/0.91.912xD322932
3x95+50CuSM0.1931.1/1.02.112xD373897
3x120+70CuSM0.1531.2/1.12.212xD404865
3x150+70CuSM0.1241.4/1.12.312xD455862
3x185+95CuSM0.09911.6/1.12.512xD497293
3x240+120CuSM0.07541.7/1.22.712xD569407
4x10CuRE1.830.71.812xD18698
4x16CuRE1.150.71.812xD21974
4x16CuRMV1.150.71.812xD21995
4x25CuRMV0.7270.91.812xD251469
4x35CuSM0.5240.91.812xD261818
4x50CuSM0.38711.912xD292354
4x70CuSM0.2681.1212xD333268
4x95CuSM0.1931.12.112xD374341
4x120CuSM0.1531.22.312xD415429
4x150CuSM0.1241.42.412xD466637
4x185CuSM0.09911.62.612xD518188
4x240CuSM0.07541.72.812xD5710609
5x10CuRE1.830.71.812xD20829
5x16CuRE1.150.71.812xD221169
5x16CuRMV1.150.71.812xD231188
5x25CuRMV0.7270.91.812xD271795
5x35CuRMV0.5240.91.812xD312363
5x50CuRMV0.3871212xD353154
5x70CuSM0.2681.12.112xD384146
5x95CuSM0.1931.12.312xD425516
5x120CuSM0.1531.22.412xD476805