Home
Low Voltage Cables

NA2X2Y

The NA2X2Y cable is a durable low-voltage cable with an aluminium conductor, PE insulation, and an HDPE sheath. It has been developed for fixed installations under increased mechanical stress and is particularly suitable for demanding industrial and energy infrastructure applications.

NA2X2Y
NA2X2Y

Request a Quote

Get technical specifications and pricing for your project.

By submitting you agree to our privacy policy

Optimal for mechanically demanding applications

The NA2X2Y complies with DIN VDE 0276-603 (HD 603) and is designed for fixed installation indoors, in cable ducts, underground, in water, or outdoors. It is primarily used in power plants, industrial facilities, and switching stations as well as local distribution networks – wherever robust cables are needed that can withstand high mechanical stress during installation and operation.

Construction and properties

The electrical conductor consists of aluminium, available as solid round (RE), stranded round (RM), or sector-shaped (SE/SM). The cores are PE-insulated, stranded together, and protected by a common EPDM sheath. The outer sheath is made of HDPE, black, UV-resistant, and highly resistant to abrasion, pressure, and moisture – ideal for long-term installations in demanding environments.

Application benefits

NA2X2Y cables provide a technically robust and cost-efficient solution for power distribution in networks with increased requirements. Their high mechanical strength and weather resistance make them the first choice for demanding infrastructure applications in the energy and industrial sectors.

Technical Specifications

General Data

Bending radius (mm)
15/12xD mm
CPR class
Fca
Maximal operating conductor temperature (°C)
90 °C
Maximal short-circuit temperature (°C)
250 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-20 °C
Operating temperature range (°C)
-35-+90 °C
Rated voltage (kV)
0.6/1 kV
Self-extinguishing of single cable
no
Test voltage (kV)
4 kV

0.6/1 kV

Voltage
0.6/1 kV
Test voltage
4 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
90 °C
Short-circuit temperature (max.)
250 °C
Minimum laying temperature
-20 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeRI [Ohm/km]Wi [mm]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x16AlRE1.910.71.812xD10104
1x25AlRE1.20.91.812xD12144
1x35AlRE0.8680.91.812xD13179
1x50AlRMV0.64111.812xD14232
1x70AlRMV0.4431.11.812xD16309
1x95AlRMV0.321.11.812xD18394
1x120AlRMV0.2531.21.812xD20479
1x150AlRMV0.2061.41.812xD22587
1x185AlRMV0.1641.61.812xD24722
1x240AlRMV0.1251.71.812xD26908
1x300AlRMV0.11.81.812xD291102
1x400AlRMV0.007821.912xD321398
1x500AlRMV0.0652.2212xD361763
3x16AlRE1.910.71.812xD19454
3x25AlRE1.20.91.812xD22634
3x35AlRE0.8680.91.812xD25788
3x50AlSM0.64111.812xD26870
3x70AlSM0.4431.11.912xD301170
3x95AlSM0.321.1212xD331463
3x120AlSM0.2531.22.112xD391802
3x150AlSM0.2061.42.312xD412184
3x185AlSM0.1641.62.412xD452647
3x240AlSM0.1251.72.612xD513362
3x35+16AlRE0.8680.9/0.71.812xD25855
3x70+35AlSM0.2681.1/0.91.912xD322828
3x95+50AlSM0.1931.1/1.02.112xD373757
3x120+70AlSM0.1531.2/1.12.212xD404707
3x150+70AlSM0.1241.4/1.12.312xD455675
3x185+95AlSM0.09911.6/1.12.512xD497071
3x240+120AlSM0.07541.7/1.22.712xD569138
4x10AlRE1.830.71.812xD18642
4x16AlRE1.150.71.812xD21910
4x25AlRMV0.7270.91.812xD251391
4x35AlRMV0.5240.91.812xD281834
4x50AlSM0.38711.912xD292255
4x70AlSM0.2681.1212xD333158
4x95AlSM0.1931.12.112xD374200
4x120AlSM0.1531.22.312xD415259
4x150AlSM0.1241.42.412xD466439
4x185AlSM0.09911.62.612xD517967
4x240AlSM0.07541.72.812xD5710324
5x10AlRE1.830.71.812xD20767
5x16AlRE1.150.71.812xD221100
5x25AlRMV0.7270.91.812xD271676
5x35AlRMV0.5240.91.812xD312266
5x50AlSM0.3871212xD332877
5x70AlSM0.2681.12.112xD383979
5x95AlSM0.1931.12.312xD425342
5x120AlSM0.1531.22.412xD476625