The NY2Y is an especially robust low-voltage cable for fixed installation under high mechanical demands – whether underground, in water, or in industrial environments. Thanks to its material combination, it is perfectly suited for a wide range of application conditions.

NY2Y
NY2Y

Request a Quote

Get technical specifications and pricing for your project.

By submitting you agree to our privacy policy

Reliable under heavy load

The NY2Y is a low-voltage cable for use in power plants, industrial facilities, switching stations, and local distribution networks. It is suitable for fixed installation indoors, in cable ducts, outdoors, in water, and underground – wherever strong mechanical stress is expected during installation and operation. The construction complies with TP PRAKAB 16/03 based on VDE 0276-603.

Detailed construction

The cable consists of a copper conductor, available as solid round (RE), stranded round (RM), or sector-shaped stranded (SM). The PVC core insulation ensures electrical safety, while the cores are stranded together and protected by a common EPDM sheath. The outer sheath made of HDPE (black, UV-resistant) makes the NY2Y particularly resistant to abrasion, moisture, and environmental influences.

Typical applications

NY2Y is ideally suited for applications with increased requirements for mechanical strength and weather resistance. Typical fields of use include power distribution in industrial plants, power stations, or transformer stations – but also in environments with moisture, direct sunlight, or chemical exposure.

Technical Specifications

General Data

Bending radius (mm)
15/12xD mm
CPR class
Fca
Maximal operating conductor temperature (°C)
70 °C
Maximal short-circuit temperature (°C)
300 mm2: +140 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-5 °C
Operating temperature range (°C)
-35-+70 °C
Rated voltage (kV)
0.6/1 kV
Self-extinguishing of single cable
no
Test voltage (kV)
4 kV

0.6/1 kV

Voltage
0.6/1 kV
Test voltage
4 kV
Operating temperature range
-35-+70 °C
Conductor temperature (max.)
70 °C
Short-circuit temperature (max.)
300 mm2: +140 °C
Minimum laying temperature
-5 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeRI [Ohm/km]Wi [mm]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x10CuRE1.8311.812xD10157
1x16CuRE1.1511.812xD11219
1x25CuRMV0.7271.21.812xD12329
1x35CuRMV0.5241.21.812xD14429
1x50CuRMV0.3871.41.812xD15565
1x70CuRMV0.2681.41.812xD17772
1x95CuRMV0.1931.61.812xD191042
1x120CuRMV0.1531.61.812xD201278
1x150CuRMV0.1241.81.812xD221571
1x185CuRMV0.099121.812xD251947
1x240CuRMV0.07542.21.812xD272514
1x300CuRMV0.06012.41.912xD303130
1x400CuRMV0.0472.6212xD343972
1x500CuRMV0.03662.82.112xD375043
3x10CuRE1.8311.812xD18589
3x16CuRE1.1511.812xD20810
3x25CuRMV0.7271.21.812xD241227
3x35CuSM0.5241.21.812xD251464
3x50CuSM0.3871.41.812xD281887
3x70CuSM0.2681.4212xD312584
3x95CuSM0.1931.62.112xD363448
3x120CuSM0.1531.62.212xD384199
3x150CuSM0.1241.82.312xD435178
3x185CuSM0.099122.512xD476381
3x240CuSM0.07542.22.712xD538264
3x35+16CuSM/RE0.5241.2/1.01.812xD271698