Home
Low Voltage Cables

NAYCWY

The NAYCWY cable is a shielded low-voltage cable with an aluminium conductor and a concentric copper conductor. It has been specifically developed for applications requiring additional protection against contact voltages – such as in industrial networks, local grids, or power distribution systems.

NAYCWY
NAYCWY

Request a Quote

Get technical specifications and pricing for your project.

By submitting you agree to our privacy policy

Designed for increased safety requirements

The NAYCWY complies with DIN VDE 0276-603 (HD 603) and is suitable for use in power plants, industrial facilities, switching stations, and local networks. It can be permanently installed – indoors, in cable ducts, outdoors, underground, or in water. Thanks to its concentric conductor, it offers additional protection in case of mechanical damage and enables safe potential equalization.

Technical construction

The electrical conductor consists of aluminium, available as stranded round (RM), sector-shaped solid (SE), or stranded (SM). The PVC core insulation and a common EPDM sheath protect the stranded cores. On top lies a concentric conductor made of bare copper wires with copper tape counter helix – ideally usable as PE or PEN conductor. A black UV-resistant PVC sheath reliably seals the cable from the outside.

Application and special features

NAYCWY cables are used wherever electrical safety and shielding are required. The concentric conductor does not need to be separated when connecting to branch joints, which simplifies installation. This makes the cable particularly suitable for modern low-voltage networks with increased requirements for operational safety and contact protection.

Technical Specifications

General Data

Bending radius (mm)
15/12xD mm
CPR class
Eca
Maximal operating conductor temperature (°C)
70 °C
Maximal short-circuit temperature (°C)
160 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-5 °C
Operating temperature range (°C)
-35-+70 °C
Rated voltage (kV)
0.6/1 kV
Self-extinguishing of single cable
IEC 60332-1-2
Test voltage (kV)
4 kV

0.6/1 kV

Voltage
0.6/1 kV
Test voltage
4 kV
Operating temperature range
-35-+70 °C
Conductor temperature (max.)
70 °C
Short-circuit temperature (max.)
160 °C
Minimum laying temperature
-5 °C
Minimum storage temperature
-35 °C
CPR class
Eca
Flame retardant
IEC 60332-1-2
Config.Cond.ShapeRI [Ohm/km]Wi [mm]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
2x16/16AlRE1.9111.812xD21651
3x16/16AlRE1.9111.812xD22710
3x25/16AlRMV1.21.21.812xD26969
3x25/25AlRMV1.21.21.812xD261028
3x35/16AlRMV0.8681.21.812xD281173
3x35/16AlSM0.8681.21.812xD261034
3x35/35AlRE0.8681.21.812xD281235
3x35/35AlSM0.8681.21.812xD261139
3x50/25AlSM0.6411.41.912xD291309
3x50/50AlSE0.6411.41.912xD281377
3x50/50AlSM0.6411.41.912xD291441
3x70/35AlSM0.4431.4212xD331740
3x70/70AlSE0.4431.4212xD341881
3x70/70AlSM0.4431.4212xD341948
3x95/50AlSM0.321.62.212xD382243
3x95/95AlSM0.321.62.212xD382529
3x120/70AlSM0.2531.62.312xD412699
3x120/120AlSE0.2531.62.312xD402915
3x120/120AlSM0.2531.62.312xD413011
3x150/70AlSM0.2061.82.412xD463242
3x150/150AlSE0.2061.82.412xD443531
3x150/150AlSM0.2061.82.412xD463674
3x185/95AlSM0.16422.612xD503925
3x185/185AlSE0.16422.612xD484313
3x185/185AlSM0.16422.612xD504492
3x240/120AlSM0.1252.22.812xD565018
4x16/10AlRE1.9111.812xD24802
4x16/16AlRE1.9111.812xD24808
4x25/16AlRE1.21.21.812xD271090
4x25/16AlRMV1.21.21.812xD281141
4x35/16AlRE0.8681.21.812xD301327
4x35/16AlSM0.8681.21.812xD281253
4x50/25AlSM0.6411.4212xD331691
4x50/35AlSE0.6411.4212xD311637
4x70/35AlSE0.4431.42.112xD352012
4x70/35AlSM0.4431.42.112xD362125
4x95/50AlSE0.321.62.312xD392631
4x95/50AlSM0.321.62.312xD412760
4x95/95AlSM0.321.62.312xD423047
4x120/70AlSE0.2531.62.412xD443280
4x120/70AlSM0.2531.62.412xD463407
4x150/70AlSE0.2061.82.612xD483870
4x150/70AlSM0.2061.82.612xD514062
4x150/120AlSM0.2061.82.612xD514297
4x150/150AlSE0.2061.82.612xD484263
4x150/150AlSM0.2061.82.612xD514455
4x185/95AlSE0.16422.812xD534775
4x185/95AlSM0.16422.812xD564995
4x240/120AlSM0.1252.2312xD626235