The NA2XY cable is a robust low-voltage cable with an aluminium conductor, PE insulation, and a PVC sheath. It is designed for fixed installation under increased mechanical stress and is particularly suitable for power distribution in industrial and public supply networks.

NA2XY
NA2XY

Request a Quote

Get technical specifications and pricing for your project.

By submitting you agree to our privacy policy

For demanding network applications

The NA2XY complies with DIN VDE 0276-603 (HD 603) and is ideal for fixed installation in indoor spaces, cable ducts, outdoors, in water, or underground. Typical areas of application include power plants, industrial facilities, and switching stations as well as local distribution networks, where mechanical stress during operation must be considered.

Technical construction

The conductor is made of aluminium, available as solid round (RE) or stranded round (RM). The cores are insulated with PE (polyethylene), which provides excellent electrical insulation and high thermal resistance. The black PVC sheath is UV-resistant and reliably protects against moisture and environmental influences.

Fields of application

NA2XY cables are the right choice for stable power distribution under mechanically demanding conditions. They provide an economical, durable solution for utilities, industry, and plant operators who rely on proven technology and high resilience.

Technical Specifications

General Data

Bending radius (mm)
15/12xD mm
CPR class
Eca
Maximal operating conductor temperature (°C)
90 °C
Maximal short-circuit temperature (°C)
250 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-5 °C
Operating temperature range (°C)
-35-+90 °C
Rated voltage (kV)
0.6/1 kV
Self-extinguishing of single cable
IEC 60332-1-2
Test voltage (kV)
4 kV

0.6/1 kV

Voltage
0.6/1 kV
Test voltage
4 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
90 °C
Short-circuit temperature (max.)
250 °C
Minimum laying temperature
-5 °C
Minimum storage temperature
-35 °C
CPR class
Eca
Flame retardant
IEC 60332-1-2
Config.Cond.ShapeRI [Ohm/km]Wi [mm]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x16AlRMV1.910.71.812xD10136
1x25AlRMV1.20.91.812xD12182
1x35AlRMV0.8680.91.812xD13222
1x50AlRMV0.64111.812xD14275
1x70AlRMV0.4431.11.812xD16358
1x95AlRMV0.321.11.812xD18448
1x120AlRMV0.2531.21.812xD20538
1x150AlRMV0.2061.41.812xD22654
1x185AlRMV0.1641.61.812xD24797
1x240AlRMV0.1251.71.812xD26991
1x300AlRMV0.11.81.812xD291194
1x400AlRMV0.077821.912xD321504
1x500AlRMV0.06052.2212xD361889
3x16AlRE1.910.71.812xD19513
3x25AlRE1.20.91.812xD22703
3x35AlRE0.8680.91.812xD25868
3x50AlSM0.64111.812xD26955
3x70AlSM0.4431.11.912xD301274
3x95AlSM0.321.1212xD331584
3x120AlSM0.2531.22.112xD391951
3x150AlSM0.2061.42.312xD412354
3x185AlSM0.1641.62.412xD452832
3x240AlSM0.1251.72.612xD513597
3x25+16AlRE1.20.9/0.71.812xD23770
3x35+16AlRE0.8680.9/0.71.812xD25940
3x50+25AlSM/RE0.6411.0/0.91.812xD291142
3x70+35AlSM/RE0.4431.1/0.91.912xD331509
3x95+50AlSM0.321.1/1.02.112xD371859
3x120+70AlSM0.2531.2/1.12.212xD402245
3x150+70AlSM0.2061.4/1.12.312xD452720
3x185+95AlSM0.1641.6/1.12.512xD493310
3x240+120AlSM0.1251.7/1.22.712xD564202
4x16AlRMV1.910.71.812xD21611
4x25AlRE1.20.91.812xD24823
4x35AlRE0.8680.91.812xD271015
4x35AlSM0.8680.91.812xD26960
4x50AlRMV0.64111.912xD321385
4x50AlSE0.64111.912xD271115
4x50AlSM0.64111.912xD291192
4x70AlSE0.4431.1212xD321501
4x95AlSE0.321.12.112xD351901
4x95AlSM0.321.12.112xD372012
4x120AlSE0.2531.22.312xD392376
4x150AlSE0.2061.42.412xD432827
4x150AlSM0.2061.42.412xD463007
4x185AlSE0.1641.62.612xD483466
4x240AlSE0.1251.72.812xD544373
4x240AlSM0.1251.72.812xD574648
5x16AlRE1.910.71.812xD23688
5x25AlRE1.20.91.812xD26955
5x35AlRE0.8680.91.812xD291181
5x50AlSM0.6411212xD331543
5x70AlSM0.4431.12.112xD382030
5x95AlSM0.321.12.312xD422604
5x120AlSM0.2531.22.412xD473159