NA2XS(FL)2Y

The NA2XS(FL)2Y cable is a longitudinally watertight medium-voltage cable with an aluminium conductor, XLPE insulation, and a combined Al/PE sheath. It has been specifically developed for power supply networks that demand high mechanical strength and reliable protection against water ingress.

NA2XS(FL)2Y
NA2XS(FL)2Y

Request a Quote

Get technical specifications and pricing for your project.

By submitting you agree to our privacy policy

Designed for use in power supply networks

The NA2XS(FL)2Y complies with standards DIN VDE 0276-620, HD 620 S2 and IEC 60502. It is ideal for installation in power supply networks (utilities), indoors, in cable ducts, outdoors, in soil, and in water. Thanks to its longitudinally watertight design and Al/PE sheath construction, it remains operational even when damaged – water ingress is effectively limited to the affected area.

Technical construction

The cable features a multi-stranded aluminium conductor (Class 2 according to VDE 0295 / IEC 60228), surrounded by XLPE insulation with a tightly bonded outer conductive layer. A conductive, longitudinally watertight tape and a copper wire screen with counter helix ensure reliable field control. The cable is also equipped with a longitudinally watertight aluminum tape that is laminated to the black PE sheath. The result: high protection against mechanical stress and moisture ingress.

Properties and applications

The NA2XS(FL)2Y cable is suitable for underground installation, free from silicone and cadmium, and suited for environments with high mechanical stress. It withstands temperatures up to +90 °C in operation and up to +250 °C under short-circuit conditions. Thanks to its partial discharge-free design and water barrier, it is particularly well suited for critical supply areas in power infrastructure.

Technical Specifications

General Data

CPR class
Fca
Flame retardant
no
Maximal operating conductor temperature (°C)
+90 °C
Maximal short-circuit temperature (°C)
+250 °C
Minimal storage temperature (°C)
-35 °C
Minimal temperature for laying (°C)
-20 °C
Operating temperature range (°C)
-35-+90 °C
Shape of conductor
RM

6/10 kV

Voltage
6/10 kV
Test voltage
21 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
+90 °C
Short-circuit temperature (max.)
+250 °C
Minimum laying temperature
-20 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeCap [uF/km]DI [mm]RI [Ohm/km]Wi [mm]Ibl [A]Ibe [A]Ik [kA]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x35/16AlRM0.2215.30.8683.41601453.32.150025643
1x50/16AlRM0.2516.40.6413.41831714.72.152026712
1x70/16AlRM0.2817.90.4433.42282086.62.140527796
1x95/16AlRM0.3119.40.323.427824892.158029902
1x120/16AlRM0.3420.90.2533.432128311.32.1600301009
1x150/25AlRM0.3622.30.2063.436431514.22.1640321193
1x185/25AlRM0.423.90.1643.441835717.52.1660331341
1x240/25AlRM0.4426.20.1253.449441322.72.1720361546
1x300/25AlRM0.4828.30.13.456846628.42.1760381797
1x400/35AlRM0.5431.40.07783.466052937.82.1820412222
1x500/35AlRM0.6134.60.06053.476760247.32.1880442599
1x630/35AlRM0.67380.04693.486169059.62.1940473062
1x800/35AlRM0.7642.30.03673.497676475.62.41040523686
1x1000/35AlRM0.8446.20.02913.41187852942.41120564372

12/20 kV

Voltage
12/20 kV
Test voltage
42 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
+90 °C
Short-circuit temperature (max.)
+250 °C
Minimum laying temperature
-20 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeCap [uF/km]DI [mm]RI [Ohm/km]Wi [mm]Ibl [A]Ibe [A]Ik [kA]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x50/16AlRM0.1720.60.6415.51851724.72.160030876
1x70/16AlRM0.1922.10.4435.52312106.62.164032982
1x95/16AlRM0.2123.60.325.528025192.1660331101
1x120/16AlRM0.2325.10.2535.532328511.32.1700351217
1x150/25AlRM0.2526.50.2065.536631914.22.1720361412
1x185/25AlRM0.2728.10.1645.542036117.52.1760381568
1x240/25AlRM0.330.40.1255.549641722.72.1800401792
1x300/25AlRM0.3232.50.15.556947128.42.1840422020
1x400/35AlRM0.3635.60.0785.566053537.82.1900452493
1x500/35AlRM0.438.80.0615.576660947.32.1980492903
1x500/50AlRM0.438.80.0615.576660947.32.1980493059
1x630/35AlRM0.4442.20.0475.586670559.62.4780523383
1x800/35AlRM0.4946.50.0375.598476775.62.4840563858
1x1000/35AlRM0.5550.40.02915.51187863942.41220614824

18/30 kV

Voltage
18/30 kV
Test voltage
63 kV
Operating temperature range
-35-+90 °C
Conductor temperature (max.)
+90 °C
Short-circuit temperature (max.)
+250 °C
Minimum laying temperature
-20 °C
Minimum storage temperature
-35 °C
CPR class
Fca
Flame retardant
no
Config.Cond.ShapeCap [uF/km]DI [mm]RI [Ohm/km]Wi [mm]Ibl [A]Ibe [A]Ik [kA]Wm [mm]Rbv [mm]Ø [mm]G [kg/km]
1x50/16AlRM0.1325.60.64181871744.72.1700351100
1x70/16AlRM0.1527.10.44382322136.62.1740371213
1x95/16AlRM0.1628.60.32828225492.1760381339
1x120/16AlRM0.1730.10.253832528911.32.1800401463
1x150/25AlRM0.1931.50.206836732214.22.1820411660
1x185/25AlRM0.233.10.164842136417.52.1860431837
1x240/25AlRM0.2235.40.125849642222.72.1900452049
1x300/25AlRM0.2437.50.1856847628.42.1940472336
1x400/35AlRM0.2740.60.0778865954137.82.11000502842
1x500/35AlRM0.2943.80.0605876461647.32.41080543269
1x630/35AlRM0.3247.20.0469886669259.62.41120563590
1x800/35AlRM0.3651.50.0367898477075.62.41200604284
1x1000/35AlRM0.3955.40.029181196878942.41340675327